Air Conditioning Basics: A/C 101

The Thermal Expansion Valve: Superheat

 

After leaving the Filter/Dryer, the refrigerant/oil mixture then flows to the Thermal Expansion Valve (TXV), again through leak-tight plumbing lines and fittings. The TXV, generally fitted directly to the Evaporator, is merely a more sophisticated version of the Expansion Valve shown in Figure 1. It is called a "Thermal" expansion valve because the device senses the temperature of the chilled air or refrigerant associated with the Evaporator and automatically and continually adjusts its internal orifice size (and, therefore, refrigerant flow rate) to maintain optimum Evaporator effectiveness and also to protect the Compressor from ingesting un-evaporated liquid.

Specifically, the job of the TXV is to maintain as much of the internal surface of the Evaporator in contact with boiling (evaporating) cold refrigerant as possible, but also to make sure that all of the refrigerant has evaporated into vapor form before it leaves the Evaporator. Further, as a safety factor, the TXV must control the flow of refrigerant to the Evaporator so that at the very end of the evaporation process, there is enough "warm" evaporator surface to heat the departing refrigerant gas above its boiling point by, say, 10 Fº. This vapor-heating process is known as "superheating" and is important primarily to insure that liquid refrigerant does not enter the compressor and cause hydraulic damage through attempting the compression of a liquid. In the most simple terms, the TXV avoids complete "flooding" of the Evaporator so there is some room left for superheating the refrigerant gas.

Specifically, the TXV functions by moving a small tapered needle stem in and out of a companion passage in response to a differential pressure. The differential pressure arises from both the pressure exerted by the Sensing Bulb (which contains refrigerant) and the pressure within the Evaporator itself. This differential, in addition to commands from the Control, is what determines the physical size of the metering orifice and, therefore, the actual amount of flow of refrigerant to the Evaporator.

As indicated earlier, when the refrigerant flows through the Expansion Valve (here, the TXV), it undergoes a very significant reduction in pressure. This process results in some of the warm liquid refrigerant actually bursting into the vapor phase ("flashing") as it passes through the valve. As this occurs, the remaining and now low pressure and liquid refrigerant becomes quite cold. This cold and mostly liquid refrigerant then flows directly into the Evaporator.

 

Back